What is the input voltage range for this power module?
The input voltage range for the Siemens 6SL3210-1PE26-0UL0 power module is 380-480 V ±10%.
What is the output power for low and high overload?
For low overload, the output power is 30 kW, and for high overload, the output power is 22 kW.
What is the maximum output current for this power module?
The maximum output current for the Siemens 6SL3210-1PE26-0UL0 power module is 90 A.
What is the pulse frequency of this power module?
The pulse frequency of the Siemens 6SL3210-1PE26-0UL0 power module is 4 kHz.
What is the cooling method used in this power module?
The Siemens 6SL3210-1PE26-0UL0 power module uses internal air cooling.
What is the maximum installation altitude for this power module?
The maximum installation altitude for the Siemens 6SL3210-1PE26-0UL0 power module is 1000 m (3280.84 ft) above sea level without derating.
What is the degree of protection for this power module?
The Siemens 6SL3210-1PE26-0UL0 power module has a degree of protection of IP20 / UL open type.
What is the maximum motor cable length for shielded and unshielded cables?
For the Siemens 6SL3210-1PE26-0UL0 power module, the maximum motor cable length is 200 m (656.17 ft) for shielded cables and 300 m (984.25 ft) for unshielded cables.
What is the operating temperature range for low and high overload?
For low overload, the operating temperature range is -20°C to 40°C (-4°F to 104°F), and for high overload, the operating temperature range is -20°C to 50°C (-4°F to 122°F).