What type of output does this Emerson part provide?
This Emerson part provides an analog output of 4-20 mA HART across 8 channels.
What are the power specifications for this part?
The power specifications include 12 VDC at 150 mA for the field circuit, 24 VDC at 300 mA for bussed field power, and 24 VDC at 23 mA per channel.
What environmental conditions can this part operate under?
This part can operate in ambient temperatures ranging from -40°C to +70°C, with a relative humidity of 5 to 95% non-condensing.
What are the shock and vibration specifications for this part?
The shock specification is 10g ½ sinewave for 11 milliseconds, and the vibration specification is 1mm peak to peak from 2 to 13.2Hz and 0.7g from 13.2 to 150Hz.
Is this part suitable for use in hazardous areas?
Yes, this part is suitable for use in hazardous areas and complies with various certifications such as FM12ATEX0090U and IECEx FMG 12.0035U.
Can this part be removed or inserted while the system power is energized?
This part cannot be removed or inserted with system power energized unless the area is known to be non-hazardous and only one unit at a time may be removed or inserted.
Does this part require calibration?
No, this part does not require calibration.
Are there any specific instructions for installation in hazardous areas?
Yes, this product has specific instructions for installation, removal, and operation in hazardous areas. Refer to the DeltaV™ Scalable Process System Zone 2 Installation Instructions and the DeltaV™ M-Series Hardware Installation and Reference manual.
What is the IP rating of this part?
This part has an IP20 rating.
Are there any user-serviceable parts in this unit?
No, this unit contains no user-serviceable parts and should not be disassembled for any reason.