What is the primary function of this part?
The primary function of the Schneider VW3A4505 is to reduce current harmonics in variable speed drives by acting as a DC choke with an inductance of 3.2 mH and a rated current of 14.3 A.
What are the compatible ranges for this part?
The Schneider VW3A4505 is compatible with the Altivar 61 and Altivar 71 ranges of inverter drives.
What are the dimensions and weight of this part?
The Schneider VW3A4505 has dimensions of 134 mm in height, 96 mm in width, and 120 mm in depth, with a net weight of 2.2 kg.
What is the IP degree of protection for this part?
The Schneider VW3A4505 has an IP20 degree of protection, making it suitable for environments where it is protected from solid objects greater than 12.5 mm in size.
What is the maximum operating altitude for this part?
The Schneider VW3A4505 can operate at altitudes up to 1000 meters without current derating, and between 1000 to 3000 meters with a current derating of 1% per 100 meters.
What are the electrical connection specifications for this part?
The Schneider VW3A4505 requires a power supply terminal with a connection capacity of 2.5 mm² (AWG 12) and an earth circuit terminal with a connection capacity of 10 mm² (AWG 6).
What is the ambient air temperature range for operation?
The Schneider VW3A4505 can operate in ambient air temperatures ranging from -10°C to 50°C without current derating, and from 50°C to 60°C with a current derating of 2.2% per °C.
What is the supply frequency range for this part?
The Schneider VW3A4505 is designed to operate with a supply frequency range of 50 to 60 Hz.